Case Study: Chinese Restaurant in Shopping Mall

Published: 2023-07-24 09:41Views:

1. Leakage situation in the project
The restaurant is located on the top floor of a shopping mall in Zhongshan, Guangdong. Below it is a popular cinema with a high customer flow. However, the kitchen and ceiling have been experiencing water leakage issues for a long time, particularly around the exhaust fans and serving hatches, which significantly affects the restaurant's operations.


图片_20230724102152.jpg

"Leakage around the vicinity of the exhaust fan."

图片_20230724102157.jpg


图片_20230724102202.jpg

2. Causes of the project leakage

After a thorough investigation by our technical team, the leakage issues have been found to be caused by the following factors:

a. The rooftop exhaust fan and ventilation openings were not properly waterproofed, or the waterproofing layer was damaged. When it rains, water easily seeps through the cracks around the rooftop exhaust fan.

b. The additional layer in the kitchen was not waterproofed, causing water to leak through the additional layer and around the exhaust fan when water flows through.


图片_20230724102441.jpg


c. The structure board of the serving hatches and masonry were not treated with waterproofing, resulting in water seeping through the corners, causing trouble for the kitchen and ceiling.


3. Maintenance Plan

Simply injecting grout from below to the floor can provide short-term effectiveness, but it won't be a lasting solution. As water will continue to slowly seep into the concrete from the cracks above, leakage will likely occur again in other places. Therefore, it is necessary to start from the source of the leakage, blocking the water outside and sealing the root cause of the leakage.

  1. a. Solution for serving hatches: First, open up the leaking cracks and use leak-stopping material to fill and block the cracks. Then, apply Qinglong adhesive sealing compound using a one-layer cloth and two-layer coating technique to achieve overall sealing.

  2. 图片_20230724115509.jpg

  3. 图片_20230724115515.jpg

  4. b. Solution for exhaust fans and ventilation openings:
    Remove the existing protective layer and expose the original structure board.

  5. 图片_20230724135809.jpg

  6. From the inside, inject grout at the joint between the circular beam and the structure board to fill and compact the small gaps.

  7. 图片_20230724141131.jpg

  8. Fill the external gaps with leak-stopping material in a circular manner,

  9. 图片_20230724141238.jpg

  10. and then apply Qinglong adhesive sealing compound using a one-layer cloth and two-layer coating technique.

  11. 图片_20230724141322.jpg

  12. Once confirmed no further leakage,

  13. 图片_20230724141417.jpg

  14. proceed to restore the concrete filling.

图片_20230724141420.jpg






Recommendation